Does anyone know how many amps the fuse in the plug is rated for? If I buy this product, should I consider buying extra fuses?

asked on July 16, 2014


I called Bestek. They tell me that there is no user-accessible fuse in this inverter. There's a 40 Amp (!!!) fuse soldered into the circuit board but none integrated into the cigarette lighter adapter.
StevenHB
· April 3, 2015
1 of 1 found this helpful. Do you?
| Report abuse

Thank you for calling them. That’s what I wanted to know. If there was a fuse in the plug in part.

Miss B
· January 21, 2019
Are you sure you want to report this comment?

The 40 amp fuse is likely on the DC side of the board. Watts = volts x current. 300 watts is 25 amps on the DC side. Consider that power supplies aren't 100% efficient, then also consider that fuses are sometimes sized for up to 150% of maximum load. So a 40A fuse would make perfect sense if it is on the DC side. If it… see more The 40 amp fuse is likely on the DC side of the board. Watts = volts x current. 300 watts is 25 amps on the DC side. Consider that power supplies aren't 100% efficient, then also consider that fuses are sometimes sized for up to 150% of maximum load. So a 40A fuse would make perfect sense if it is on the DC side. If it's on the AC side, then yes i would say that's a problem. see less The 40 amp fuse is likely on the DC side of the board. Watts = volts x current. 300 watts is 25 amps on the DC side. Consider that power supplies aren't 100% efficient, then also consider that fuses are sometimes sized for up to 150% of maximum load. So a 40A fuse would make perfect sense if it is on the DC side. If it's on the AC side, then yes i would say that's a problem.